TACO ZVC404-EXP-4 INSTRUCTION SHEET Pdf Download (2024)

SUPERSEDES: New

Plant ID# 9300-2880

Wiring Diagram

WHITE

120 VAC

INPUT

BLACK

WHITE

120 VAC

INPUT

BLACK

Optional System

and/or DHW and/or

Secondary Circulators

PUMP END

ZONE 4 PUMP

SWITCH

END SWITCH

X

X

N/O COM N/C

HOT

120

SYSTEM

VAC

PUMP

DHW

PUMP

NEUTRAL

SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.

DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.

SECONDARY PUMP COMES ON WHEN ANY ZONE CALLS EXCEPT PRIORITY ZONE.

Operation/External Diagnostics: When any thermostat calls for heat,

the appropriate zone valve is energized and the yellow light goes on.

When the zone valve is fully open, the red light goes on and energizes

the end switch relay. The green light should always be on, indicating

that power is connected.

Priority Operation: When the priority dip switch is set to ON and the

priority zone is actuated, all other zones will stop operation until pri-

ority zone is satisfied. When not switched to priority, all zones will

operate independently.

Mode Operation: When the dip switch is set to NORMAL, the end

switch relay will be energized if any zone is in operation. When the switch

is set to RESET, the end switch relay will only be energized if the priority

zone is in operation, or through the operation of a plug-in reset control.

Post Purge Operation: When the dip switch is set to ON, the priori-

ty zone output will stay energized for 2 minutes after its thermostat or

aquastat is satisfied, but not operate the boiler.

Priority Protection Operation: When the dip switch is set to ON, and

if the priority zone calls continuously for more than one hour, power

is returned to all the other zones, allowing each zone to function inde-

pendently. Once the priority zone is satisfied, the control's auto-reset is

activated and the priority zone is again allowed to have priority for up

to one hour starting from when it calls next.

Pump Exercise Operation: When the dip switch is set to ON, the solid

state timer cycles all the zone valves and circulating pumps that are

attached to the Expandable Zone Valve Control at the selected time

interval. The time interval can be set for the valves and pumps to run

for either 30 seconds every 2 weeks or for 4 minutes every 24 hours.

End Switches (Dry Contacts): The main end switch closes when any

zone thermostat calls for heat and the mode switch is set to NORMAL.

The main end switch also closes when the mode switch is set to RESET

and a PC Series boiler reset power control is calling for heat. The priori-

ty end switch closes only when the priority zone thermostat or aquastat

is calling for heat.

Specifications:

PRODUCT

NUMBER

INPUT

NUMBER

OF ZONES

VOLTAGE

ZVC404-EXP-4

4 with Priority

120/60/1 VAC, 3A

1

The pump end switches are rated

hp, 5 amps at 120 VAC. The main and priority end switch connections

6

are rated 24 VAC, 1 amp. All thermostat and zone valve connections supply a 24 VAC class 2 output.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that

may cause undesired operation.

Instruction Sheet

ZVC404-EXP-4 Zone Valve Control

TO: "TT" ON BOILER WITH

TO: "TT" ON BOILER

POWER

CONTROLS

FUSE

A

5 AMP

24 VAC

FUSE

5 AMP

ACCESSORY

B

24 VAC

PUMP END

ZONE 4 PUMP

SWITCH

END SWITCH

X

X

N/O COM N/C

TO

CIRCULATOR

DRY

CONTACTS

SECONDARY

PUMP

MAX 24 VAC

TYPE 1 ENCLOSURE

OUTPUT @ 25°C

WIDTH HEIGHT

1

24 VA per Zone

12

"

8"

4

40 VA per Transformer

Powered from Transformer A

DHW "TT" INPUT

X X X X

A B C R W C R W C R W C R W C 1 2

MAIN

PRIORITY

EXPANSION

END SWITCH

MASTER

SLAVE

PRIORITY ON

OFF

PORT

RESET

NORMAL

POST PURGE ON

OFF

PRIORITY PROTECTION ON

OFF

PUMP EXERCISE ON

OFF

30 SEC/2 WK

4 MIN/24 HOUR

24 VAC ZONE VALVES

ZONE 1

1 2 3 4

JUMPER

3 & 4

1

2

3

2 WIRE

ZONE VALVE

TACO

(NO END SWITCH)

3 WIRE

MUST USE JUMPER

ZONE VALVE

Powered from Transformer A

Expansion Connections: Set the expansion switch to MASTER on the

switching relay that has the designated priority zone or is utilizing the

PC Series plug-in option. Set all other daisy chained controls to SLAVE.

Using thermostat wire (18-22 gauge) connect between terminals A, B,

C on the master control to the corresponding A, B, C on the SLAVE con-

trol(s). Controls may be daisy chained up to 20 zoning panels using any

combination of -EXP controls (120 zones if all are 6 zone panels).

Thermostat Input (24 vac):

R

Hot side of transformer. Connect to R on thermostat.

W

Switched R signal from thermostat. Connect to W on

thermostat.

C

Common side of transformer. Connect to COM on

thermostat (optional).

NET Network terminals 1 & 2 are tied together for wiring convenience

when using communicating style thermostats (optional).

Power Input (120 vac):

Connect neutral (white) leads on transformers to 120 volts ac

neutral power supply.

Connect hot (black) leads on transformers to 120 volts ac

hot power supply.

Pump End Switch (Dry Contacts):

Connect hot power supply to the right side of the pump end switch

terminal on board.

Connect hot input lead of the circulator to the left side of the pump

end switch terminal on board.

Zone 4 Pump End Switches (Dry Contacts): See Diagram.

N/O Normally open terminal of the priority zone relay.

COM Common terminal of the priority zone relay.

N/C Normally closed terminal of the priority zone relay.

End Switch Pump Neutral Connections:

Connect neutral power supply directly to neutral lead on circulator(s).

WARNING: Wiring connections must be made in accordance with all

applicable electrical codes. Use copper wire only. 120 VAC wiring must have

DEPTH

a minimum temperature rating of 75°C. Failure to follow this instruction

3"

can result in personal injury or death and/or property damage. 12-18 gauge

wire recommended for 120 VAC connections, 14-22 gauge wire for thermo-

stat connections, and 14-22 gauge wire for 24 VAC source connections.

EFFECTIVE: May 1, 2010

Powered from Transformer B

THERMOSTATS (24 VAC)

ZONE 1 ZONE 2 ZONE 3 ZONE 4 NET

THERMOSTATS (24 VAC) PRIORITY

ZVC 404-EXP-4

FOUR ZONE EXPANDABLE

ZONE VALVE CONTROL

PRIORITY

ZONE 2

ZONE 3

ZONE 4

1 2 3 4

1 2 3 4

1 2 3 4

JUMPER

3 & 4

PRIORITY

ZONE

MOTOR

END

SWITCH

NOTE: When a circulator is used

on the priority zone instead of a

zone valve, jumper 3 and 4 of

the priority zone.

4 WIRE

ZONE VALVE

(POWER OPEN,

SELF CLOSING)

Powered from Transformer B

102-399

INDIRECT

WATER HEATER

AQUASTAT OR

THERMOSTAT

LED

INDICATORS

POWER

VALVE 1

T STAT 1

T STAT 2

VALVE 2

VALVE 3

T STAT 3

T STAT 4

VALVE 4

SEE NOTE

TACO ZVC404-EXP-4 INSTRUCTION SHEET Pdf Download (2024)

References

Top Articles
Latest Posts
Article information

Author: Ms. Lucile Johns

Last Updated:

Views: 6696

Rating: 4 / 5 (61 voted)

Reviews: 84% of readers found this page helpful

Author information

Name: Ms. Lucile Johns

Birthday: 1999-11-16

Address: Suite 237 56046 Walsh Coves, West Enid, VT 46557

Phone: +59115435987187

Job: Education Supervisor

Hobby: Genealogy, Stone skipping, Skydiving, Nordic skating, Couponing, Coloring, Gardening

Introduction: My name is Ms. Lucile Johns, I am a successful, friendly, friendly, homely, adventurous, handsome, delightful person who loves writing and wants to share my knowledge and understanding with you.